This heat exchanger calculator works out the log mean temperature difference and the area you need. Enter the hot and cold inlet and outlet temperatures, counterflow or parallel flow, the overall heat transfer coefficient and the hot-side flow and specific heat, and it shows the LMTD, the duty in kW and the required area. If you know the cold flow instead of its outlet, it works out the outlet from an energy balance. Paste several operating cases to compare them. It runs in your browser.
| Hot in/out | Cold in/out | ΔT1 | ΔT2 | LMTD |
|---|---|---|---|---|
| 90/60 °C | 20/40 °C | 50 | 40 | 44.81 |
| 80/40 °C | 15/35 °C | 45 | 25 | 34.03 |
| 90/50 °C | 20/30 °C | 60 | 30 | 43.28 |
| 100/40 °C | 20/30 °C | 70 | 20 | 39.91 |
| 90/60 °C | 20/50 °C | 40 | 40 | 40.00 |
The effective average temperature difference driving heat transfer: (ΔT1 − ΔT2) ÷ ln(ΔT1/ΔT2).
It keeps a larger temperature difference along the exchanger, giving a higher LMTD and smaller area for the same duty.
A correction for multi-pass shell-and-tube units, from charts; 1 for pure counterflow or parallel flow.
Water–water plate exchangers are typically 3,000–7,000 W/m²K and shell-and-tube 800–1,500; use the manufacturer's figure when you have it.
No. Everything runs in your browser.
End temperature differences: counterflow ΔT1 = Th,in − Tc,out and ΔT2 = Th,out − Tc,in; parallel flow ΔT1 = Th,in − Tc,in and ΔT2 = Th,out − Tc,out. LMTD = (ΔT1 − ΔT2) ÷ ln(ΔT1/ΔT2). Duty Q = ṁ × cp × (Th,in − Th,out) on the hot side. Required area A = Q ÷ (U × F × LMTD), with F the correction for multi-pass arrangements. The cold outlet can be found from the energy balance given the cold flow and cp. Batch mode reads operating cases.