Room Lighting (Lux) Calculator

This lighting calculator tells you how many light fittings a room needs. Enter the room size, the height of the fittings above the desk, the target illuminance — 500 lux for offices, 300 for classrooms, 100 for corridors — and the lumens and watts of your fitting, and it uses the lumen method to give the number of fittings, a grid layout with spacings, the lux achieved and the power density. Paste every room in a building to plan the whole job. It runs in your browser.

Typical maintained illuminance

SpaceLux
Office desk work500
Conference room500
Classroom300
Retail sales area300
Workshop, general300
Fine assembly750
Warehouse storage150
Corridor100

When to use it

  1. Plan LED panels for an office.
  2. Check a classroom meets its lighting target.
  3. Compare fittings with different lumen outputs.
  4. Estimate lighting for every room in a building.
  5. Check power density against an energy code.

How to Use

  1. Enter room length, width and fitting height above the desk.
  2. Choose the room type or a target lux.
  3. Enter lumens and watts per fitting, UF and MF.
  4. Read fittings, layout and achieved lux; paste rooms for a building.

Features

  1. Lumen method
  2. Room types with typical lux
  3. Grid layout and spacing
  4. Achieved lux and W/m²
  5. Room index
  6. Batch CSV
  7. 100% client-side

FAQs

How many lux does an office need?

Around 500 lux on desks; classrooms about 300, corridors about 100.

How do I calculate the number of lights?

Lights = lux × area ÷ (lumens per light × utilisation factor × maintenance factor). 500 lux in 80 m² with 4,000 lm fittings at UF 0.6 and MF 0.8 needs 21.

What is the utilisation factor?

The share of lamp lumens reaching the working plane, from the fitting's photometric data; 0.4–0.7 is typical.

What is the maintenance factor?

Allowance for dirt and lumen depreciation over time, usually 0.7–0.9 for LEDs.

Is anything uploaded?

No. Everything runs in your browser.

Technical Details

The lumen method gives the number of fittings N = E × A ÷ (Φ × UF × MF): target illuminance in lux, room area in m², lumens per fitting, utilisation factor and maintenance factor. The room index K = L × W ÷ (Hm × (L + W)) uses the fitting height above the working plane. The suggested grid is the fewest fittings at or above N with similar spacing along both walls, and the achieved lux and power density in W/m² follow. Batch mode reads rooms from a CSV.