This lighting calculator tells you how many light fittings a room needs. Enter the room size, the height of the fittings above the desk, the target illuminance — 500 lux for offices, 300 for classrooms, 100 for corridors — and the lumens and watts of your fitting, and it uses the lumen method to give the number of fittings, a grid layout with spacings, the lux achieved and the power density. Paste every room in a building to plan the whole job. It runs in your browser.
| Space | Lux |
|---|---|
| Office desk work | 500 |
| Conference room | 500 |
| Classroom | 300 |
| Retail sales area | 300 |
| Workshop, general | 300 |
| Fine assembly | 750 |
| Warehouse storage | 150 |
| Corridor | 100 |
Around 500 lux on desks; classrooms about 300, corridors about 100.
Lights = lux × area ÷ (lumens per light × utilisation factor × maintenance factor). 500 lux in 80 m² with 4,000 lm fittings at UF 0.6 and MF 0.8 needs 21.
The share of lamp lumens reaching the working plane, from the fitting's photometric data; 0.4–0.7 is typical.
Allowance for dirt and lumen depreciation over time, usually 0.7–0.9 for LEDs.
No. Everything runs in your browser.
The lumen method gives the number of fittings N = E × A ÷ (Φ × UF × MF): target illuminance in lux, room area in m², lumens per fitting, utilisation factor and maintenance factor. The room index K = L × W ÷ (Hm × (L + W)) uses the fitting height above the working plane. The suggested grid is the fewest fittings at or above N with similar spacing along both walls, and the achieved lux and power density in W/m² follow. Batch mode reads rooms from a CSV.