This transformer calculator gives the full-load current on both windings from the kVA rating and voltages, for three-phase or single-phase units. Add the nameplate impedance to estimate the maximum fault current at the secondary terminals. A table shows currents for standard ratings from 15 to 3,000 kVA at your voltages, and you can paste a whole transformer list. It runs in your browser.
| kVA | Primary A | Secondary A |
|---|---|---|
| 100 | 5.2 | 139 |
| 250 | 13.1 | 348 |
| 500 | 26.2 | 696 |
| 1,000 | 52.5 | 1,391 |
| 1,600 | 84.0 | 2,226 |
| 2,500 | 131.2 | 3,478 |
Three-phase: kVA × 1,000 ÷ (1.732 × V). A 1,000 kVA transformer at 415 V carries about 1,391 A.
The voltage needed to drive full-load current through a shorted secondary, as a percentage of rated voltage. Lower %Z means higher fault current.
No. It assumes an infinite supply; source and cable impedance reduce it.
Choose single-phase and it uses kVA × 1,000 ÷ V.
No. Everything runs in your browser.
Full-load current = kVA × 1,000 ÷ (√3 × line voltage) for three-phase, or kVA × 1,000 ÷ voltage for single-phase, on each winding. With the nameplate impedance, the maximum secondary fault current ≈ secondary full-load current × 100 ÷ %Z, assuming an infinite source. A table lists currents for standard kVA ratings at the chosen voltages, and batch mode reads a list of transformers.