This U-value calculator works out how well a wall, roof or floor keeps heat in. List the layers from outside to inside with their thicknesses — brick, block, insulation, plasterboard, an air gap — choose the element, and it adds each layer's resistance and the surface resistances to give the total R-value (metric and imperial) and the U-value, plus the heat loss for an area and temperature difference. Use a built-in conductivity or type your own. Paste several build-ups to compare them. It runs in your browser.
| Build-up | R (m²K/W) | U (W/m²K) |
|---|---|---|
| Solid brick 230 + plaster | 0.50 | 2.00 |
| Brick, 100 mineral wool, block | 3.23 | 0.31 |
| Block + 100 EPS external | 3.47 | 0.29 |
| Concrete + 80 PIR | 4.01 | 0.25 |
| Timber frame, 140 glass wool | 4.32 | 0.23 |
U = 1 ÷ (sum of each layer's thickness ÷ conductivity + surface resistances).
Modern regulations often ask for about 0.18–0.30 W/m²K for new walls; an uninsulated solid brick wall is around 2.
R is resistance (higher is better); U is its inverse, heat flow per m² per degree (lower is better).
No. Studs, ties and joists raise the real U-value; use your national method for compliance.
No. Everything runs in your browser.
Each layer's thermal resistance R = thickness ÷ conductivity λ; an unventilated cavity adds 0.18 m²K/W. The total adds the internal surface resistance (ISO 6946: 0.13 for walls, 0.10 for roofs with upward heat flow, 0.17 for floors) and the external 0.04. U = 1 ÷ total R in W/m²K; imperial R = RSI × 5.678. Heat loss = U × area × temperature difference. Layers are typed as material: thickness in mm, with a built-in list of common λ values or a custom one after @. Batch mode reads build-ups per row.