This AWG to mm² converter translates American wire gauge into metric cross-section and back. Enter a gauge such as 12 or 4/0, or an area such as 2.5 mm², and get the area, diameter, kcmil, copper resistance per kilometre and per 1,000 feet, and the nearest standard metric cable at least as large. A full chart covers 24 AWG to 4/0. Importers and electricians can convert a whole size list at once. It runs in your browser.
| AWG | mm² | Diameter mm | Ω/km copper | Next metric |
|---|---|---|---|---|
| 18 | 0.82 | 1.02 | 20.95 | 1 mm² |
| 16 | 1.31 | 1.29 | 13.17 | 1.5 mm² |
| 14 | 2.08 | 1.63 | 8.29 | 2.5 mm² |
| 12 | 3.31 | 2.05 | 5.21 | 4 mm² |
| 10 | 5.26 | 2.59 | 3.28 | 6 mm² |
| 8 | 8.37 | 3.26 | 2.06 | 10 mm² |
| 6 | 13.30 | 4.12 | 1.30 | 16 mm² |
| 4 | 21.15 | 5.19 | 0.82 | 25 mm² |
| 2 | 33.63 | 6.54 | 0.51 | 35 mm² |
3.31 mm². The nearest standard metric size at least as large is 4 mm².
No. 14 AWG is 2.08 mm², smaller; 2.5 mm² sits between 14 and 12 AWG.
The gauge counted drawing steps: more steps made thinner wire. Every 3 gauges roughly halves the area.
Four-aught, the largest AWG size (107 mm²); beyond it sizes are given in kcmil.
No. Everything runs in your browser.
AWG diameter d = 0.127 mm × 92^((36 − n) ÷ 39), with 1/0 = 0, 2/0 = −1, 3/0 = −2 and 4/0 = −3; area = π ÷ 4 × d². kcmil = mm² ÷ 0.5067. Copper resistance at 20 °C = 0.017241 ÷ area Ω per metre. Converting from mm² gives the smallest AWG at least that large (within 3%), and each gauge shows the nearest standard IEC metric size at least as large. Batch mode converts a column of sizes.