This power factor correction calculator sizes the capacitor bank to cut reactive power charges and free up capacity. Enter the real power, the present power factor and your target, and it shows the kVAR needed, the drop in kVA and line current, and the capacitance per phase for a star or delta bank. Paste your monthly kWh and kVArh readings to see each month's power factor and the correction it needed. It runs in your browser.
| Present PF | To 0.95 | To 0.98 |
|---|---|---|
| 0.60 | 1.005 | 1.130 |
| 0.70 | 0.692 | 0.817 |
| 0.75 | 0.553 | 0.679 |
| 0.80 | 0.421 | 0.547 |
| 0.85 | 0.291 | 0.417 |
| 0.90 | 0.156 | 0.281 |
kVAR = kW × (tan(arccos PF1) − tan(arccos PF2)). Raising 100 kW from 0.70 to 0.95 needs about 69 kVAR.
Utilities commonly penalise below 0.90 or 0.95; most plants aim for 0.95–0.98, avoiding leading power factor at light load.
A delta bank needs a third of the capacitance per phase for the same kVAR, but each capacitor sees full line voltage.
Yes, with harmonics from drives they can resonate; use detuned banks in that case.
No. Everything runs in your browser.
Capacitor reactive power Qc = P × (tan φ1 − tan φ2), where φ = arccos(PF) before and after. Current falls in proportion to the power factor improvement. Capacitance for single-phase is Qc ÷ (2πf × V²); for a three-phase bank, per phase, Qc ÷ (2πf × V_L²) in star and a third of that in delta. From a bill, PF = kWh ÷ √(kWh² + kVArh²) and the average load is kWh ÷ hours in the period, giving the kVAR needed at that load.