Power Factor Correction Calculator

This power factor correction calculator sizes the capacitor bank to cut reactive power charges and free up capacity. Enter the real power, the present power factor and your target, and it shows the kVAR needed, the drop in kVA and line current, and the capacitance per phase for a star or delta bank. Paste your monthly kWh and kVArh readings to see each month's power factor and the correction it needed. It runs in your browser.

kVAR needed per kW

Present PFTo 0.95To 0.98
0.601.0051.130
0.700.6920.817
0.750.5530.679
0.800.4210.547
0.850.2910.417
0.900.1560.281

When to use it

  1. Avoid a utility's low power factor penalty.
  2. Size an automatic capacitor bank for a plant.
  3. Free up transformer capacity.
  4. Check a capacitor quotation.
  5. Track power factor across a year of bills.

How to Use

  1. Enter real power and present and target power factor.
  2. Choose supply, voltage and frequency.
  3. Read the kVAR, current reduction and capacitance.
  4. Paste monthly kWh and kVArh to analyse bills.

Features

  1. Capacitor kVAR
  2. µF per phase, star or delta
  3. kVA and current saved
  4. Bill analysis from kWh and kVArh
  5. 50 or 60 Hz
  6. Batch CSV
  7. 100% client-side

FAQs

How do I calculate the kVAR needed?

kVAR = kW × (tan(arccos PF1) − tan(arccos PF2)). Raising 100 kW from 0.70 to 0.95 needs about 69 kVAR.

What power factor should I aim for?

Utilities commonly penalise below 0.90 or 0.95; most plants aim for 0.95–0.98, avoiding leading power factor at light load.

Star or delta capacitors?

A delta bank needs a third of the capacitance per phase for the same kVAR, but each capacitor sees full line voltage.

Can capacitors cause problems?

Yes, with harmonics from drives they can resonate; use detuned banks in that case.

Is anything uploaded?

No. Everything runs in your browser.

Technical Details

Capacitor reactive power Qc = P × (tan φ1 − tan φ2), where φ = arccos(PF) before and after. Current falls in proportion to the power factor improvement. Capacitance for single-phase is Qc ÷ (2πf × V²); for a three-phase bank, per phase, Qc ÷ (2πf × V_L²) in star and a third of that in delta. From a bill, PF = kWh ÷ √(kWh² + kVArh²) and the average load is kWh ÷ hours in the period, giving the kVAR needed at that load.