This three-phase power calculator converts between current and power for any load. Enter the line voltage and power factor, then either the current or the kW, and it shows real power, apparent power (kVA), reactive power (kVAR) and line current. It also works for single-phase. Paste every load on a distribution board — compressors, pumps, lighting, heaters — and get the board's total kW, kVA, overall power factor and current. It runs in your browser.
| Load | Current |
|---|---|
| 1 kW | 1.7 A |
| 5.5 kW | 9.3 A |
| 11 kW | 18.7 A |
| 22 kW | 37.4 A |
| 45 kW | 76.4 A |
| 90 kW | 152.8 A |
I = kW × 1,000 ÷ (√3 × V × PF). An 11 kW motor at 400 V and 0.85 PF draws about 18.7 A.
kW is the real power that does work; kVA is what the supply must carry. kVA = kW ÷ power factor.
Reactive power, which magnetises motors and transformers but does no work; it raises current and losses.
Yes. Switch the supply to single-phase and it uses P = V × I × PF.
No. Everything runs in your browser.
Three-phase real power P = √3 × line voltage × current × power factor; single-phase P = V × I × PF. Apparent power S = P ÷ PF and reactive power Q = √(S² − P²). Given kW (or hp × 0.7457) the current is P ÷ (√3 × V × PF). Board totals add kW and kVAR separately, then give total kVA, the overall power factor and the line current, assuming balanced loads.