This conduit fill calculator checks whether your wires fit. Enter the wires as counts and sizes, such as 3 x 10 and 1 x 12, choose EMT or PVC Schedule 40 and the trade size, and it shows the fill percentage against the NEC limit, the smallest conduit that works and the total wire area. A quick table shows how many wires of one size fit each conduit. Paste every run on a job to check them all. It runs in your browser.
| Wire | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in |
|---|---|---|---|---|---|
| 14 AWG | 12 | 21 | 35 | 61 | 83 |
| 12 AWG | 9 | 16 | 25 | 44 | 61 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 |
| 8 AWG | 3 | 5 | 9 | 16 | 22 |
| 6 AWG | 1 | 4 | 6 | 11 | 16 |
40% of the conduit's area for three or more conductors, 31% for two and 53% for one (NEC Chapter 9, Table 1).
Nine. Ten would exceed 40%.
Yes. Every conductor, including equipment grounds, counts toward fill.
This uses THHN/THWN areas; THW, XHHW and others are larger, so use Table 5 for them.
No. Everything runs in your browser.
Conductor areas come from NEC Chapter 9 Table 5 (THHN, THWN and THWN-2) and conduit internal areas from Table 4 (EMT and PVC Schedule 40). Table 1 limits fill to 53% of the area for one conductor, 31% for two and 40% for three or more. Fill % = total wire area ÷ conduit area; the smallest conduit is the first trade size whose limit covers the wires. The maximum number of one size per conduit applies the same limits. Batch mode reads a list of runs with their wires.