Conduit Fill Calculator

This conduit fill calculator checks whether your wires fit. Enter the wires as counts and sizes, such as 3 x 10 and 1 x 12, choose EMT or PVC Schedule 40 and the trade size, and it shows the fill percentage against the NEC limit, the smallest conduit that works and the total wire area. A quick table shows how many wires of one size fit each conduit. Paste every run on a job to check them all. It runs in your browser.

Maximum THHN wires in EMT

Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in
14 AWG1221356183
12 AWG916254461
10 AWG510162838
8 AWG3591622
6 AWG1461116

When to use it

  1. Pick the conduit size for a new circuit.
  2. Check whether another circuit fits an existing conduit.
  3. Size a feeder conduit with mixed wire sizes.
  4. Check a job's conduit schedule before ordering.
  5. Study for an electrician's exam.

How to Use

  1. Enter the wires, such as 3 x 10, 1 x 12.
  2. Choose EMT or PVC and the trade size.
  3. Read the fill % and the smallest conduit.
  4. Paste a list of runs to check them all.

Features

  1. EMT and PVC Schedule 40
  2. THHN/THWN wire areas
  3. 53/31/40% limits
  4. Smallest conduit
  5. Max wires per size
  6. Batch CSV
  7. 100% client-side

FAQs

What is the maximum conduit fill?

40% of the conduit's area for three or more conductors, 31% for two and 53% for one (NEC Chapter 9, Table 1).

How many 12 AWG THHN fit in 1/2 inch EMT?

Nine. Ten would exceed 40%.

Does the ground wire count?

Yes. Every conductor, including equipment grounds, counts toward fill.

What about other insulation types?

This uses THHN/THWN areas; THW, XHHW and others are larger, so use Table 5 for them.

Is anything uploaded?

No. Everything runs in your browser.

Technical Details

Conductor areas come from NEC Chapter 9 Table 5 (THHN, THWN and THWN-2) and conduit internal areas from Table 4 (EMT and PVC Schedule 40). Table 1 limits fill to 53% of the area for one conductor, 31% for two and 40% for three or more. Fill % = total wire area ÷ conduit area; the smallest conduit is the first trade size whose limit covers the wires. The maximum number of one size per conduit applies the same limits. Batch mode reads a list of runs with their wires.