This psychrometric calculator works out moist air properties from two readings. Enter the dry bulb temperature and one of relative humidity, wet bulb or dew point — in °C or °F — and your altitude, and it shows the relative humidity, dew point, wet bulb, humidity ratio, enthalpy, specific volume and density. Paste a sensor log of temperature and humidity to add dew point and enthalpy to every row. It runs in your browser.
| Dry bulb | RH | Dew point | Wet bulb | g/kg | kJ/kg |
|---|---|---|---|---|---|
| 20 °C | 50% | 9.3 °C | 13.8 °C | 7.26 | 38.6 |
| 25 °C | 50% | 13.9 °C | 17.9 °C | 9.88 | 50.3 |
| 25 °C | 70% | 19.1 °C | 21.0 °C | 13.92 | 60.6 |
| 30 °C | 60% | 21.4 °C | 23.8 °C | 16.04 | 71.2 |
| 35 °C | 40% | 19.4 °C | 23.9 °C | 14.13 | 71.5 |
About 13.9 °C. Surfaces colder than that will collect condensation.
The temperature a wetted thermometer reaches through evaporative cooling; at 25 °C and 50% RH it is about 17.9 °C.
Lower pressure means more water per kg of air at the same RH, changing humidity ratio and enthalpy.
Heat content of the air per kg; the difference across a coil gives its total cooling or heating load.
No. Everything runs in your browser.
Saturation vapour pressure uses the Hyland–Wexler equations from ASHRAE Fundamentals (over water above 0 °C, over ice below). Humidity ratio W = 0.621945 pw/(p − pw); relative humidity = pw/pws(t); dew point is the temperature where pws equals pw; wet bulb is solved from the ASHRAE psychrometric equation; enthalpy h = 1.006t + W(2501 + 1.86t) kJ/kg dry air; specific volume v = 0.287042(t + 273.15)(1 + 1.607858W)/p. Pressure comes from altitude with p = 101.325(1 − 2.25577×10⁻⁵Z)^5.2559 kPa. Batch mode converts a temperature and RH log.