Cable Ampacity and Derating Calculator

This cable ampacity calculator finds how much current a conductor can carry after derating, under the US National Electrical Code or IEC 60364. Choose the code, conductor and insulation, the size, the ambient temperature and how many conductors or circuits share the raceway, and it shows the table rating, each correction factor and the derated ampacity, plus the smallest size that carries your load. Paste a whole cable schedule to check every circuit at once. It runs in your browser; check against the code edition your inspector uses.

NEC Table 310.16, copper, 30 °C, up to 3 conductors

Size60 °C75 °C90 °C
14 AWG152025
12 AWG202530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
2 AWG95115130
1/0125150170
4/0195230260

When to use it

  1. Check a circuit's wire size against its breaker.
  2. Derate conductors in a hot attic or rooftop conduit.
  3. Size cables when many circuits share one conduit.
  4. Check a cable schedule before submitting drawings.
  5. Compare copper and aluminium feeders.

How to Use

  1. Choose NEC or IEC and the conductor type.
  2. Pick the size, ambient temperature and number of grouped conductors.
  3. Read the derated ampacity and the smallest size for your load.
  4. Paste a cable schedule to check every circuit.

Features

  1. NEC Table 310.16
  2. IEC 60364-5-52 PVC copper
  3. Ambient and grouping derating
  4. Small-conductor breaker limits
  5. Smallest size for a load
  6. Cable schedule CSV
  7. 100% client-side

FAQs

How do I derate wire for temperature?

Multiply the table ampacity by √((insulation rating − ambient) ÷ (rating − 30)). A 90 °C conductor at 40 °C ambient keeps 91% of its rating.

How many wires in a conduit before derating?

Under the NEC, more than three current-carrying conductors: 4–6 keep 80%, 7–9 keep 70%, 10–20 keep 50%.

Can I use the 90 °C column?

For derating, yes, but the final ampacity can't exceed the rating of the terminals, usually 60 °C or 75 °C (NEC 110.14(C)).

Why is 12 AWG limited to 20 A?

NEC 240.4(D) limits the breaker on 14, 12 and 10 AWG copper to 15, 20 and 30 A.

Is anything uploaded?

No. Everything runs in your browser.

Technical Details

NEC mode uses Table 310.16 (copper or aluminium, 60, 75 or 90 °C columns, up to three current-carrying conductors at 30 °C), the 310.15(C)(1) adjustment for 4–6 (80%), 7–9 (70%), 10–20 (50%), 21–30 (45%), 31–40 (40%) and more (35%) conductors, and the 240.4(D) overcurrent limits for 14, 12 and 10 AWG. IEC mode uses 60364-5-52 values for PVC-insulated copper by reference method (B1 in conduit on a wall, C clipped direct) and two or three loaded conductors, with the bunched-cable grouping factors. Ambient correction uses √((Tc − Ta) ÷ (Tc − 30)). Derated ampacity = table value × ambient factor × grouping factor; the smallest size is the first whose derated rating covers the load.