This pipe pressure drop calculator works out how much pressure a pipe loses for a given flow, using the Darcy–Weisbach equation with the Colebrook friction factor. Enter the inside diameter, length, flow and pipe material, plus any fittings and height change, and it shows the pressure drop in kPa, bar, psi and metres of head, the velocity, Reynolds number and friction factor, and how much comes from friction, fittings and elevation. Change density and viscosity for other liquids. Paste every segment of a system to size a pump. It runs in your browser.
| Inside Ø | Flow | Velocity | Pressure drop |
|---|---|---|---|
| 15.8 mm | 0.2 L/s | 1.02 m/s | 105.9 kPa |
| 26.6 mm | 0.5 L/s | 0.90 m/s | 43.2 kPa |
| 40.9 mm | 1.5 L/s | 1.14 m/s | 39.0 kPa |
| 52.5 mm | 2.5 L/s | 1.15 m/s | 29.2 kPa |
| 77.9 mm | 6 L/s | 1.26 m/s | 21.0 kPa |
| 102.3 mm | 10 L/s | 1.22 m/s | 14.1 kPa |
ΔP = f × (L/D) × ρv²/2, with f from the Colebrook equation.
About 1–3 m/s in most systems; higher gets noisy and erodes fittings.
A loss coefficient: a 90° elbow is about 0.3–0.9, an open gate valve about 0.2 and a globe valve about 10.
Yes. Enter the fluid's density and viscosity.
No. Everything runs in your browser.
Velocity v = flow ÷ (π/4 × D²) and Reynolds number Re = ρvD/μ. The Darcy friction factor is 64/Re for laminar flow and otherwise solved from the Colebrook–White equation 1/√f = −2 log10(ε/3.7D + 2.51/(Re√f)) by iteration. Pressure drop ΔP = f × (L/D) × ρv²/2 for the pipe, plus ΣK × ρv²/2 for fittings and ρgΔz for elevation. Roughness presets cover steel, galvanised and cast iron, plastics, copper and concrete. Batch mode reads one pipe segment per row.