This UPS backup time calculator tells you how long your inverter battery will run your fans, lights and router during load-shedding. Enter the battery's Ah and voltage, how many batteries are wired in series, the battery type and the inverter's efficiency, then build the load from a list of common appliances or your own wattages. The result shows the backup in hours and minutes, the usable energy after a safe depth of discharge (50% for lead-acid, 70% for tubular, 90% for lithium), and the current drawn from the battery, with a warning when a lead-acid bank is pushed too hard to deliver its rated capacity. Set a target number of hours and it works out the Ah you need instead. To compare several batteries before buying, paste a CSV of options and each one is calculated side by side. It is free, runs in your browser, and nothing you enter is uploaded.
| Battery | Usable Wh | 150 W load | 300 W load | 500 W load |
|---|---|---|---|---|
| 150 Ah lead-acid (50%) | 765 | 5 h 6 min | 2 h 33 min | 1 h 32 min |
| 200 Ah tubular (70%) | 1,428 | 9 h 31 min | 4 h 46 min | 2 h 51 min |
| 100 Ah LiFePO4, 12.8 V (90%) | 979 | 6 h 32 min | 3 h 16 min | 1 h 58 min |
Multiply battery Ah × voltage × number of batteries × depth of discharge × inverter efficiency, then divide by the load in watts.
A 12 V 200 Ah tubular battery at 70% depth of discharge and 85% efficiency gives about 4 hours 45 minutes on a 300 W load.
Older batteries hold less than their rating, and lead-acid batteries deliver less than their rated Ah at high current. Keep the C-rate below 0.2 for a closer match.
About 50% for flooded or AGM lead-acid, 70% for tubular and 80–90% for LiFePO4 lithium, to protect cycle life.
No. The calculator runs in your browser and nothing is sent anywhere.
Stored energy is battery Ah × voltage × number of batteries in series. Usable energy multiplies that by the depth of discharge that preserves cycle life (50% for flooded or AGM lead-acid, 70% for tubular, 90% for LiFePO4) and by the inverter's efficiency. Backup hours are usable Wh ÷ total load in watts, where the load is the sum of each appliance's watts × quantity. Battery current is load ÷ efficiency ÷ bank voltage, and the C-rate (current ÷ Ah) flags lead-acid loads above 0.2C, where Peukert's effect makes real capacity fall short of the 20-hour rating. A reverse panel solves for the Ah needed per battery to reach a target number of hours. Batch mode compares battery options row by row.