This voltage drop calculator works out how many volts a cable loses over its length and the smallest wire size that keeps the drop within your limit. Choose single-phase, three-phase or DC, enter the supply voltage, the load as current or watts with a power factor, the one-way cable length in meters or feet, and copper or aluminium in IEC mm² or AWG sizes. It corrects the conductor's resistance for operating temperature, then shows the drop in volts and percent, the voltage left at the load, the power wasted as heat in the cable and the minimum size that meets 3%, 5% or any limit you set. Electricians can paste a full cable schedule as CSV, with a mix of circuits, sizes and materials, and every run is checked at once. It is free, runs in your browser, and your project data is never uploaded. Remember that ampacity and protection still need checking separately.
| Size | mV per A per m | 16 A | 32 A |
|---|---|---|---|
| 1.5 mm² | 27.5 | 15.7 m | 7.8 m |
| 2.5 mm² | 16.5 | 26.1 m | 13.1 m |
| 4 mm² | 10.3 | 41.8 m | 20.9 m |
| 6 mm² | 6.88 | 62.7 m | 31.4 m |
| 10 mm² | 4.13 | 104 m | 52.3 m |
| 16 mm² | 2.58 | 167 m | 83.6 m |
For single-phase or DC, multiply 2 × one-way length × current × the cable's resistance per meter. For three-phase, use √3 instead of 2.
IEC 60364 suggests 3% for lighting and 5% for other circuits from the supply point; the US NEC recommends 3% for a branch circuit and 5% in total.
Copper's resistance rises about 0.4% per °C. A cable running at 70 °C has about 20% more resistance, and more drop, than the same cable cold.
No. The cable must also carry the current without overheating for its installation method, and be protected by a suitable breaker. Check ampacity separately.
No. Calculations run in your browser.
Conductor resistance per meter is resistivity ÷ cross-section, using 0.017241 Ω·mm²/m for copper and 0.028264 for aluminium at 20 °C, corrected to the operating temperature with coefficients of 0.00393 and 0.00403 per °C (70 °C for PVC and 90 °C for XLPE at full load). For DC and single-phase circuits the drop is 2 × one-way length × current × resistance, since current flows out and back; for balanced three-phase circuits it is √3 × length × current × resistance against the line-to-line voltage. Current can be entered directly or derived from watts as P ÷ V, P ÷ (V × PF) or P ÷ (√3 × V × PF). AWG cross-sections come from d = 0.127 mm × 92^((36 − n)/39). The minimum size is the smallest IEC mm² or AWG size whose drop stays within the chosen percentage. Reactance is ignored, which is accurate up to about 50 mm².